Chapter 3 Electrical Installation 19
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
U1
X3
Q1
Q5
W2
V1 W1
V3
U3
N3
W3
V2
U2
Q2
Q3
N2
助端子
辅
接
接
盒
线
池
接
电
连
整流器
接
连
旁路
接
连
出
接
输
连
接地
注: 如采用分离旁路,
拆
请
除旁路和整流器
入之
的
输
间
三个横向跨接母线
(
*)
* **
Auxiliary
terminal block
Battery
connections
Rectifier
connections
Bypass
connections
Earth
Output
connections
Note: For split bypass operation,
ensure that the three horizontal
busbars (*) between the bypass
input and rectifier input are removed.
ensure that the three horizontal
busbars (*) between the bypass
input and rectifier input are removed.
Figure 3-3 Power cable connections for 300/400kVA UPS
3.2 Distance From Floor To Connection Point
The distances from floor to connection points are provided in Table 3-2.
Table 3-2 Distance from floor to connection point
Minimum distance (mm)
UPS
160/200kVA
300kVA
400KVA
Rectifier AC input supply
247.5
273
273
Bypass AC input supply
247.5
273
273
UPS AC output
247.5
267.5
273
Battery power
244
300
305
Battery control and temperature compensation
325
350
350
Ground 247.5
270
274