Chapter 3  Electrical Installation      19 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
U1
X3
Q1
Q5
W2
V1 W1
V3
U3
N3
W3
V2
U2
Q2
Q3
N2
助端子

线
整流器
旁路
接地
注: 如采用分离旁路,
除旁路和整流器
入之
三个横向跨接母线
*)
* **
Auxiliary
terminal block
Battery
connections
Rectifier
connections
Bypass
connections
Earth
Output
connections
Note: For split bypass operation,
ensure that the three horizontal
busbars (*) between the bypass
input and rectifier input are removed.
 
Figure 3-3    Power cable connections for 300/400kVA UPS 
3.2   Distance From Floor To Connection Point 
The distances from floor to connection points are provided in Table 3-2. 
Table 3-2    Distance from floor to connection point 
Minimum distance (mm) 
UPS 
160/200kVA 
300kVA 
400KVA 
Rectifier AC input supply 
247.5 
273 
273 
Bypass AC input supply 
247.5 
273 
273 
UPS AC output 
247.5 
267.5 
273 
Battery power 
244 
300 
305 
Battery control and temperature compensation 
325 
350 
350 
Ground 247.5 
270 
274