Fluke 1744 User Manual

Page of 73
 
Power Quality Logger 
 Using 
the 
Logger 
 
  
15 
Logging with Voltage Converters 
The 1744/1743 Logger includes an adjustable converter ratio that enables it to 
be used with voltage converters (potential transformers, or PTs). 
Note 
When logging with voltage converters, make sure the power supply 
cables are not connected in parallel to the voltage test leads, or the 
Logger’s power consumption can reduce accuracy. 
 
The converter ratio is defined using the PQ Log software. 
Connecting the Logger 
W
 
X
 Warnings 
 
To avoid electrical shock, do not connect any part of 
the Logger to systems that have higher voltages to 
ground (earth) than are marked on the Logger. 
 
Areas between the power company meter and the 
source of the distribution system are characterized as 
CAT IV areas. To avoid electrical shock or equipment 
damage, never connect the Logger to power in CAT IV 
areas if the voltage-to-earth ground is greater than 
300 V. 
 
To avoid damaging the Logger, never connect its 
voltage measuring inputs to phase-to-phase voltages 
higher than 830 V. 
 
To avoid damaging the Logger, never connect the 
power supply leads to voltages higher than 660 V RMS 
ac. 
 
The Logger is to be used and handled only by qualified 
personnel (see page 6). 
 
Maintenance work on the Logger must be done only by 
qualified service personnel.