CyberPower ATT36A12V3S User Manual

Page of 11
 
CyberPower ATT3612V3S (Leave Behind Manual) 
Page: 7 of 11 
 
4  
OPERATION 
4.1  
Start-Up 
Make sure that the battery connector is plugged in, the battery is locked into place, and the 
battery door is closed. Plug the ATT3612V3S power supply into AC power. The LED of system 
status showing green indicates normal mode of operation. The unit is now ready to be placed 
into service. 
4.2  
Controls 
 
 
Figure 4: Front Panel LED and Controls 
One user control is present in the form of one blue button on the front cover of the BBPSU. This 
alarm-silence button will quiet the audible alarm for 24 hours. After 24 hours the alarm will 
reactivate if the fault condition has not been corrected. 
Function Symbol Type 
Location
Function 
Alarm 
Silence 
 
Push 
Front 
Cover 
Press and hold the button for 3 seconds to silence the 
audible alarm for 24 hours 
Table 1: Customer Button Operation 
4.3  
Operational LEDs 
Four status LEDs are displayed on the front panel of the BBPSU.  The operation of the BBPSU 
can be assessed using these LEDs. 
Indicator Color 
Condition 
Alarm Silence Button
Blue 
Press and hold the button for 3 seconds to silence the audible 
alarm for 24 hours. 
System Status 
Green 
Indicates normal mode of operation. 
Battery Power 
(Working) 
Green 
Indicates the battery is supplying the power. 
Battery Power (Low)
Flashing 
Green  
Battery Power is nearly depleted. Beeps four times every two 
minutes. 
Replace Battery 
Red 
Battery replacement required alarm will beep twice every 3 minutes.
Missing Battery 
Red 
Indicates that the battery is disconnected or removed. No Audible 
Alarm. 
 
Table 2: LED Indicators