Chapter 4 - Signals and Troubleshooting 
 
 
 
IV A
  
4 - 20 
DCS 500B / DCP 500B Operating Instructions 
Para-
meter 
Code 
bit 
Text on LCD of con-
trol panel CDP 31x  
Definition / explication of the signal
   
Remark
 
12 
(FIELD2_CURR_MIN_L) 
1 = motor 2 field current above min level  
 
11204 
-- ---- TC_STATUS:  
Status of the torque control sequencing 
 
 
00 
(RDY ON) 
1 = ready for closing contractor  
 
 
01 
(MAIN CONT ON) 
1 = command to close contractor  
 
 
02 
(RDY RUNNING) 
1 = ready for run command  
 
 
03 
(RUNNING) 
1 = command to release controllers  
 
 
04 
(TC_RDY_REF) 
1 = ready for reference  
 
 
05 
(TC_FIELD_CHANGE) 
1 = field reversal is active  
 
 
06 
(CONTINUOUS_CURR)  
1 = armature current is discontinuous  
 
11205 
-- ---- BC:  
Status of the current regulator.  If the value of BC is 
zero, everything is OK.  Otherwise different bits of 
BC will indicate the reason for blocking the current 
regulator  
 
 
00 
-------- 
Overcurrent  
 
 
01 
-------- 
Freewheeling unit was fired  
 
 
02 
-------- 
field reversal  
 
 
03 
-------- 
supply system  undervoltage  
 
 
04 
-------- 
12Puls only: fault 65 and 66 occurred  
 
 
05 
-------- 
12Puls only: signal via cable X18  
 
 
06 
-------- 
supply system overvoltage  
 
 
07 
-------- 
type code error  
 
 
08 
-------- 
suppression of controller at regulator change-over  
 
 
09 
-------- 
processor overload  
 
 
10 
-------- 
thyristor diagnostic running  
 
 
11 
-------- -------- 
 
 
12 
-------- 
primary (AC) or secondary (48Vdc) power failure  
 
 
13 
-------- 
synchronization signal missing  
 
 
14 
-------- 
pulse firing section not in synchronism  
 
 
15 
-------- 
not released  
 
 
 