 wire to the connector. The barrel on each connector that is closest to the center of the
fuse
 panel (barrel with a cap over it) is not used or accessed. The wire is inserted into the
connector
 and the set screw is tightened down, compressing the wire. The set screw barrel
connectors
 can accept up to #6 AWG copper wire. 
1.5
Output Voltage
The
 output voltage will be the same voltage as the applied input voltage when the fuse does not fail.
1.6
Output Connectors
Each
  output  circuit  has  two  connectors  through  which  the  output  power  is  accessed  for
connection
  to  telecommunications  equipment.  The  following  types  of  output  connectors  are
available:
 
• Screw-down
 barrier terminal strip: Eight terminals with 6-32 screws are mounted in two
barrier
  type  terminal  strips  per  bus  (one  strip  for  input  and  one  strip  for  return).  The
terminals
  are  on  0.375  inch  (9.525  mm)  centers  with  a  maximum  distance  between
barriers
 (maximum connecting terminal width) of 0.325 inch (8.255 mm). Terminals can
accept
 #12 to #22 AWG copper wire with crimp-on spade lug or ring connectors or wires
with
 the insulation stripped back. 
• Set
 screw barrel terminal strip: Eight barrel terminals are mounted in two set screw barrel
terminal
 strips per bus (one strip for input and one strip for return). The terminals are on
0.197
 inch (5.004 mm) centers. Terminals can accept #12 to #26 AWG copper wire with
insulation
 stripped back. 
1.7
Chassis Ground Connection
Two
 #10 studs mounted on 0.625 inch (15.875 mm) centers are provided for grounding the fuse
panel
  chassis.  This  chassis  ground  connection  can  be  used  to  attach  a  separate  grounding
conductor
 when mounting the fuse panel in non-grounded or non-conducting material or when
required
 by local practice. The studs can accommodate 2-hole lugs and up to #6 AWG wire.
Two
 crimp ring lug terminals for use with #10 AWG wire are enclosed with the fuse panel. The
fuse
 panel can be properly grounded using only one grounding stud.
1.8
Fuses
The
 fuse panel accommodates industry standard type 70 fuses with values from 0.02 Amp to
10.0
 Amps in any fuse position within the maximum capacity of the bus (total fuse load cannot
exceed
 bus capacity). The maximum fuse value that can be used in each fuse position is 10.0
Amps
 which is marked on the front panel.
The
 type  70 fuse  contains  a  colored  indicator  that  designates the  fuse value. When the  fuse
blows,
 the indicator extends out of the fuse to indicate that the fuse has blown. Fuse panels are
shipped
 without fuses installed. Standard type 70 fuses are available from ADC.