ADC 70 User Manual

Page of 32
ADCP-80-524 • Issue 1 • November 2001
Page 13
©
 2001, ADC Telecommunications, Inc.
1.9
Power-On Indicator
A
 visual power-on indicator (green LED) for each power bus is mounted on the front panel of
the
 fuse panel. A lighted LED indicates that power is applied to the bus input connectors. An
unlighted
 LED indicates that power is not applied to the bus input connectors. The LED can
easily
 be replaced in the field if it fails.
1.10 Fuse Alarm Indicator
A
 visual fuse alarm indicator (red LED) is provided on the front panel for each power bus. The
fuse
  alarm  indicator  lights  when  any  fuse  on  the  corresponding  bus  fails.  The  fuse  alarm
indicator
 is off when all fuses on the corresponding bus are operational. Loss of power to a bus
will
 not cause the fuse alarm indicator corresponding to that bus to be lighted. The LED can be
easily
 replaced in the field if it fails.
1.11 Alarm Contact Operation
Each
 bus contains circuitry that opens and closes a set of alarm contacts when any fuse on the
bus
 fails or when the input power to the bus is lost. These contacts may be used to open or close
a
 loop connected to an external alarm system. 
The
  alarm  circuitry  provides  Form  C  alarm  relay  contacts.  During  normal  operation,  the
normally
  open  (NO)  contacts  remain  open  and  the  normally  closed  (NC)  contacts  remain
closed.
 When a fuse fails on either bus or power to either bus is lost, the NO contacts close
creating
 a connection between NO and common (C) and the NC contacts open creating an open
circuit
 between NC and common. The current rating for each set of alarm relay contacts (three
sets
 are provided) is 1.0 Amp maximum. 
1.12 Alarm Contact Connection
Alarm
 contact connections are provided through three sets of wire wrap pins located on the rear
side
 of the fuse panel. Each set of wire wrap pins is labeled with a suggested use for monitoring
the
  fuse  panel:  audio,  visual,  and  remote.  The  wire  wrap  pins  can  accept  #22  to  #26  AWG
copper
 wire. 
1.13 Fuse Designation Strips and Perforated Cards
Plastic
 designation strips with clear plastic covers are mounted above the fuse holders for each
bus.
 Four card sheets, each with three perforated strips, are provided with the fuse panel. The
perforated
 strips may be marked with the circuit designations/fuse values for each circuit/fuse
on
  the  bus.  The  perforated  strips  are  then  inserted  into  the  designation  strips  so  that  the
information
  on  the  perforated  strip  is  positioned  above  the  corresponding  fuses.  Additional
perforated
 strip cards and plastic covers can be ordered from ADC if required.