Sanyo E11A202U User Manual

Page of 47
 
− 27 − 
 
11.4 Battery Maintenance 
 
 
CAUTION 
 
 
・ 
Internal maintenance and inspection should be performed only by technically 
qualified personnel. Electric shock, injury, burning, smoke or file could 
otherwise result. 
・ 
Batteries should be replaced periodically. Batteries used after their service life 
has passed may cause a fire. 
・ 
Never use organic chemicals such as gasoline, thinner, benzene or detergent to 
clean batteries. These can cause the casing to crack and leak, resulting in fire 
or current leakage. 
 
(1)  Battery backup time confirmation 
Refer to §11.5 “Battery Test”, and periodically perform a battery backup time test. 
Depending on the results of the test, exchange the battery. 
The default Setup menu setting is to perform an automatic battery test once every 6 
months.  
 
  (2)  Estimated battery replacement interval 
Battery service life is affected by operating conditions such as ambient temperature 
and the number of discharge cycles. Ambient temperature has a particularly strong 
influence as indicated in the following table (refer to the table to predict when 
batteries will need to be replaced according to average ambient temperature). Using 
batteries after their service life has expired can cause leakage, and in the worst case 
damage may result, so we recommend exchanging batteries early as a preventative 
and protective step. 
 
Average Ambient 
Operating Temperature 
Projected Service 
Life 
Battery Replacement 
Interval 
25°C (77°F) 
5 years 
4.5 years 
30°C (86°F) 
3.5 years 
3 years 
35°C (95°F) 
2.5 years 
2 years 
40°C (104°F) 
1.7 years 
1.5 years 
 
(3) Battery 
specifications 
The batteries in the UPS are specially designed for this application. Do not substitute 
with any other type, and do not mix new and old batteries, as shortened battery life, 
leakage, and heat could result. 
Replace batteries information: 
  HRL1234WF2FR manufactured by CSB BATTERY Co., LTD. 
 
 
(4) Battery 
disposal 
Batteries are industrial waste containing lead, a toxic material and reusable resource. 
Please cooperate by recycling when replacing or disposing of used batteries. To 
dispose of used batteries, contact an authorized industrial waste handling company, 
or repack them in their original cartons and send them to your supplier.