11.7 Bypass Breaker Reset 
 
 
CAUTION 
 
 
Always power the UPS off before resetting the bypass breaker. Failure to do 
so can cause electric shock. Be careful to avoid injury or electric shock. 
 
If the bypass breaker trips, the red ALARM indicator lights and output from the output 
terminals stops. 
Proceed as follows to reset the bypass breaker.
 
 
① 
Stop the inverter by pressing 
  and holding it for 1 second, and then set   
 MAIN MCCB  to “OFF”. 
② 
Examine if there are neither a problem nor a trouble in the equipment of the load . 
  Press the bypass breaker on the back panel of the UPS. 
  Set    MAIN MCCB    to “ON”, and then start the UPS by pressing 
  and holding it 
for 1 second. 
For details about UPS startup, see §9.1 “UPS Startup (Normal Operation)”.
 
 
 
 
UPS back panel
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note 
・ 
If you reset the bypass breaker while the UPS is powered on, the red ALARM indicator will 
remain lit until you power the UPS off. Always power the UPS off before resetting the bypass 
breaker. 
 
 
 
 
 
 
Bypass breaker
This completes the bypass breaker reset.