Schneider Electric 230 VAC User Manual

Page of 20
7
Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount
Configuration
UPS Settings
Start-up Settings
Configure these settings at initial start-up, using the display interface or APC PowerChute
®
 software.
Note: During start-up, use the display interface to configure these settings. If nothing is 
selected, the unit will use the default settings.
General Settings
Configure these settings at any time, using the display interface or APC PowerChute
®
 software.
Function
Factory Default Options
Description
Language
English
• English
• French*
• German*
• Spanish*
• Italian*
• Portuguese*
The language for the display interface.
*Language options will vary by model.
Local Power 
Quality
Good
• Good
• Fair
• Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery 
power more often to provide the cleanest power 
supply to the connected equipment.
• If Poor is selected, the UPS will tolerate more 
fluctuations in power and will go on battery power 
less often. 
If unsure of the local power quality, select Good.
Menu Type
Standard
Standard or 
Advanced
The advanced menus include all parameters. The 
Standard menus display a limited set of menus and 
options.
Function
Factory Default Options
Description
High Transfer 
Point 
120 V:
127 Vac
• 127 Vac
• 130 Vac
• 133 Vac
• 136 Vac
To avoid unnecessary battery usage, set the 
transfer point higher if the utility voltage is 
chronically high and the connected equipment 
is known to work under this condition. The 
P
OWER
 Q
UALITY
 setting will automatically 
change this setting. 
Note: Use the Advanced Menus to configure 
this setting.
208 V:
225 Vac
• 225 Vac
• 229 Vac
• 233 Vac
• 237 Vac
230 V:
253 Vac
• 253 Vac
• 257 Vac
• 261 Vac
• 265 Vac