8
Low Transfer 
Point
120 V: 
106 Vac
• 97 Vac
• 100 Vac
• 103 Vac
• 106 Vac
Set the transfer point lower if the utility 
voltage is chronically low and the connected 
equipment can tolerate this condition.This 
setting may also be adjusted using the power 
quality setting.
Note: Use the Advanced Menus to configure 
this setting.
208 V:
182 Vac
• 170 Vac
• 174 Vac
• 178 Vac
• 182 Vac
230 V:
208 Vac
• 196 Vac
• 200 Vac
• 204 Vac
• 208 Vac
Nominal Output 
Voltage
120 Vac
N/A
Set the nominal output voltage of the UPS on 
battery. This is available on 230 V models 
only.
230 Vac
208-252 Vac
Transfer 
Sensitivity
High
High, Reduced, Low Select the level of sensitivity to power events 
that the UPS will tolerate.
• High: The UPS will go on battery power 
more often to provide the cleanest power 
supply to the connected equipment.
• Low: The UPS will tolerate more 
fluctuations in power and will go on battery 
power less often. 
If the connected load is sensitive to power 
disturbances, set the sensitivity to High.
Low Battery 
Warning
120 sec
Set the value in 
seconds
The UPS will emit an audible alarm when the 
remaining runtime has reached this level.
Date of Last 
Battery 
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On
On/Off
The UPS will mute all audible alarms if this is 
set to Off or when the display buttons are 
pressed.
Battery Self-
Test Interval 
Setting
On start-up and 
every 14 days since 
the last test
• Never
• Start-up only
• Frequency of test 
(days)
The interval at which the UPS will execute a 
self-test.
Reset to Factory 
Default
No
Yes/No
Restore the UPS factory default settings.
Function
Factory Default Options
Description