IBM UPS 7500XHV User Manual

Page of 29
11
 
 2:  O
PERATION
 
 
Front Display Panel 
 
 
 
 
I
NDICATOR
 
D
ESCRIPTION 
 
Online 
 
This LED is lit when the uninterruptible power supply is supplying utility power to the 
connected equipment and performing double conversion to supply power to the con-
nected equipment. If not lit, the uninterruptible power supply is either not turned on, or 
is supplying battery power. When flashing, the uninterruptible power supply is running 
an internal self-test. 
On Battery  
 
This LED is lit when the uninterruptible power supply is supplying battery power to the 
connected equipment.  
Bypass 
 
This LED is lit when the unit is sending utility power directly to the connected equip-
ment. Bypass mode operation is the result of an internal fault, an overload condition, or 
a user-initiated command (performed manually through the manual bypass switch). 
Battery operation is not available while the uninterruptible power supply is in bypass 
mode. See Troubleshooting
Fault 
 
This LED is lit when the uninterruptible power supply detects an internal fault. See 
Troubleshooting
Overload 
 
This LED is lit and the uninterruptible power supply emits a sustained alarm tone when 
the connected loads are drawing more than the uninterruptible power supply power 
rating. See Troubleshooting
Replace Battery 
 
Failure of a battery self-test causes the uninterruptible power supply to emit short beeps 
for one minute and this LED to be lit. See Troubleshooting. 
F
EATURE
 
F
UNCTION
 
Power On 
 
Press this button to turn on the uninterruptible power supply. (Additional capabilities 
will be described later in the document.) 
Power Off 
 
Press this button to turn off the uninterruptible power supply. 
Self-Test  
Automatic: The uninterruptible power supply performs a self-test automatically when 
turned on, and every two weeks thereafter (by default). During the self-test, the uninter-
ruptible power supply briefly operates the connected equipment on battery. 
If the uninterruptible power supply fails the self-test, the replace battery LED is lit and 
immediately returns to online operation. The connected equipment is not affected by a 
failed test. Allow the battery to recharge for 24 hours and perform another self-test. If it 
fails, the battery must be replaced. 
Manual: Press and hold the 
 button for a few seconds to initiate the self-test.