IBM UPS 7500XHV User Manual

Page of 29
13
 
UPS 7500XHV Model: 
 
Number of Battery Packs 
 
Load (W) 
Internal 
+1 
+2 
+4 
50  
7.56 
13.83 
21.50 
37.68 
100 6.00 10.93 
17.06 
29.83 
200 4.16 7.65 11.93 
20.90 
300  3.16 5.83 9.11 16.00 
400  2.51 4.68 7.36 12.89 
500  2.11 3.91 6.12 10.75 
600  1.80 3.33 5.25 9.23 
700  1.56 2.90 4.52 8.00 
800  1.38 2.56 4.01 7.03 
900  1.23 2.30 3.61 6.38 
1000 1.10 2.08 3.28 5.78 
1200 
55 1.73 2.74 4.83 
1400 
47 1.50 2.35 4.16 
1600 
41 1.28 2.05 3.63 
1800 
36 1.13 1.81 3.23 
2000 
32 1.00 1.61 2.90 
2500 
24 
48 1.28 2.28 
3000 
19 
39 1.05 1.88 
3400 
17 
34 
55 1.65 
4000 
13 
28 
46 1.36 
5000 
10 
21 
35 1.06 
6000 
16 
28 
52 
Recharge 
Hours 
10 
17 
UPS 10000XHV Model: 
 
Number of Battery Packs 
 
Load (W) 
Internal 
+1 
+2 
+4 
50  
7.56 
13.83 
21.55 
37.68 
100 6.00 10.93 
17.06 
29.83 
200 4.16 7.65 11.93 
20.90 
300  3.16 5.83 9.11 16.00 
400  2.55 4.68 7.35 12.88 
500  2.11 3.91 6.12 10.75 
600  1.80 3.33 5.24 9.21 
700  1.56 2.90 4.56 8.03 
800  1.38 2.56 4.05 7.11 
900  1.23 2.30 3.61 6.38 
1000 1.16 2.08 3.28 5.78 
1200 
55 1.73 2.73 4.85 
1400 
47 1.50 2.35 4.16 
1600 
41 1.28 2.05 3.63 
1800 
36 1.13 1.81 3.23 
2000 
32 1.00 1.61 2.90 
2500 
24 
48 1.28 2.28 
3000 
19 
39 1.05 1.88 
3400 
17 
34 
55 1.65 
4000 
13 
28 
46 1.36 
5000 
10 
21 
35 1.06 
6000 
16 
28 
52 
7000 
13 
23 
44 
8000 
11 
20 
37 
Recharge 
Hours 
10 
17