Liebert UPS User Manual

Page of 37
 
10
GXT6000T / 10000T - 208 UPS ONLY 
 
Models whose part number ends with a “208” are NOT fitted with an isolating 
output transformer and are NOT separately derived sources under the NEC.  The 
output L1 terminal is connected to the input L1 terminal and must not be 
connected to ground at the UPS (see NEC 250-5d, 250-26, 250.91, 250.92). 
 
GXT6000T-208 CONNECTIONS 
CONNECTION 
CURRENT 
RATING 
Recommended 
Wire Size 
Recommended External 
Overcurrent Protection 
INPUT 
28 AMPS 
8 AWG (10 mm²) 
40 AMPS 
OUTPUT 
26 AMPS 
8 AWG (10 mm²) 
BATTERY 
23 AMPS 
8 AWG (10 mm²) 
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
 
 
GXT10000T-208 CONNECTIONS 
CONNECTION 
CURRENT 
RATING 
Recommended 
Wire Size 
Recommended External 
Overcurrent Protection 
INPUT 
45 AMPS 
6AWG (16 mm²) 
60 AMPS 
OUTPUT 
43 AMPS 
6AWG (16 mm²) 
BATTERY 
37 AMPS 
6AWG (16 mm²) 
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS 
 
INPUT 
UTILITY 
OUTPUT 
NOTE 4 
OPTIONAL 
BATTERY 
 
L
1
 
L
2
 
 
L
1
 
L
2
 
 
 
 
 
 
 
 
 
 
 
 
NOTE 5
NOTE 6
INPUT TO UPS 
NOTE 1
 
OUTPUT TO LOAD 
 NOTE 2
 
OPTIONAL 
BATTERIES 
NOTE 3 
208
208