Connecting the UPS Power cables 
Power cables connect to screw terminals on a terminal block that is located 
behind the rear mounted cable box (see figure). Permanent wiring must be 
routed to the cable box using appropriate materials as required by local codes. 
Connection of optional remote battery cabinets 
Full installation instructions are provided with these cabinets. Safety/EMC 
certification limits the use of these terminals to Liebert supplied options. 
Properly grounded (earthed) equipment provide multiple benefits 
High quality ground (earth) connections are required for the equipment ground 
conductors (protective earth) and grounding electrode conductor (power system 
earth connection) to reduce electrical noise and provide for safe operation of the 
UPS and connected loads.  Conduit used alone without a grounding conductor 
wire is not an acceptable connection. Size ground (protective earth) conductors 
equal to circuit conductors.