Chapter 6  Maintenance 
73 
6.1.7  Monitoring system 
1. Background communication 
The monitoring system of this UPS system provides one RS232 port and one 
RS485 port (the definition of the port is in Section 3.4.3), several input and output 
dry contacts (refer to Section 3.4.4). The user can introduce the signal to the 
nearest management office to conduct equipment management. All the data 
displayed on the panel will be monitored by background monitoring software. 
Besides, there are also MODEM and SNMP cards, which are used for MODEM and 
SNMP communication. 
1RS232 mode 
The transmission distance of RS232 mode is shorter than 15m. This RS232 
mode is suitable for the short distance monitoring required by UPS operator or 
user. 
2RS485 mode 
The J23 connector on the monitoring board is used for user’s RS485 port. 
“485+” and “485-” are used as the user’s positive terminal and negative terminal 
respectively. SHIELD terminal is used as the shielding terminal that connects the 
shielding layer. 
The transmission distance is shorter than 1000m. The user can use any 
RS485/RS232 converter(such as the OCI-6 provided by us) to realize 
networking of RS485+RS232 mode. 
3MODEM mode 
The user can monitor the UPS remotely via a MODEM and the monitoring 
software- POWERSTAR by dialing the preset telephone number. Refer to 
“Directions of MODEM” and “Directions of POWERSTAR” for details. 
4SNMP mode 
The parts of SNMP card UF-SNMP111 is compatible with 10/100M either net. 
The SNMP card supports various kinds of protocols of SNMP, TFTP, HTTP and 
TELNET and providing a solution for high speed network access method. 
The user can connect the UPS to the LAN through the SNMP card and realize 
the network management. 
Refer to “Directions of SNMP” card for details.