Liebert 1500 User Manual

Page of 59
Operation          31
Figure 28 Equalize voltage and duration settings
Fuses
Thirty-four fuses for circuit protection as described in Table 37. Except for the ABS fuse, which is 
small tube type (9/32” dia x 1-1/4” long), all fuses are of the QFF type.
Test points
Three sets of test points for applications as described in Table 38.
Table 37
Fuse
Designation
Capacity
Description
ABS
15 A
-48 V supply for the office alarm circuit(s)
ABS ALM
1/2 A
Alarm fuse for the above ABS fuse
RC1 to RC24
1-1/3 A
-48 V sense supply for the rectifiers of the system 
CONV
1/2 A
Protection for the internal converter in the controller
METER
1/2 A
Protection for the meter and selector panel if so equipped
CHG
1/2 A
Protection for internal circuitry of the controller when the CONT rotary switch 
is in the CHG VOLT position
Spare 1 and 2
0 to 5 A
For external loads as required (ex.: Helios Monitor)
BAT
1/2 A
Protection for internal circuitry of the controller when the CONT rotary switch 
is in the BAT VOLT position
CONT
1-1/3 A
Protection for the internal circuitry of the controller
Plus one unused position
Table 38
Test points
Designation
Description
CAL OUT + and -
To connect an external meter when calibrating the LED readout for current readings
VOLT + and -
To connect an external meter when adjusting the BOD, LF, LV, HF, HV, HVSD, LVD and 
LVR thresholds
PWR EXT + and -
The connect an external power supply when adjusting the LVR threshold
 VOLT
Switch #     1             2             3
0.6V
1.3V
1.9V
2.6V
3.2V
3.9V
4.6V
: switch in the ON position
 TIMER
Switch #   1     2     3     4     5     6
10 sec.
20 sec.
38 sec.
1.25 h
3.0 h
5.0 h
LOP enabled
1
2
3
4
5
6
OFF      ON
ON     OFF
1
2
3