32          Operation
4.2.2
Rear Panel
The rear panel of the Conventional Controller is provided with the connection interface features 
shown in Figure 30 and described in the following subsections.
Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controller
Terminal blocks
Six terminal blocks to interface with external wiring as follows:
• TB1: various alarm outputs to the office alarm circuits and the cabinet alarm lamp
• TB2: various alarm outputs to the office alarm circuits, and remote equalize signal input
• TB3: various alarm outputs to the office alarm circuits, and charge and discharge fuse alarm 
inputs
• TB4: various alarm outputs to the office alarm circuits, and LVD control and alarm
• TB5: various alarm outputs to the office alarm circuits, remote TR signal input, -48 V supply 
to cabinet alarm lamp and various small loads, and AUX 1 and AUX 2 alarms inputs
• TB6: -48 V supply to office alarm circuits if required, VR+ and VR- inputs, and -48 V and 
ground inputs
Refer to Figure 30 anFigure 31 for the pin assignment of terminal blocks TB1 to TB6.