Battery Mode
When the UPS is operating during a power outage, the alarm beeps once every four
seconds and the 
  indicator illuminates. When the utility power returns, the UPS
switches to Normal mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the 
 indicator flashes and the
alarm beeps twice every two seconds. Immediately complete and save your work to
prevent data loss and similar difficulties. When utility power is restored after the UPS
shuts down, the UPS automatically restarts.
Sleep Mode
If the UPS is on battery for approximately five minutes and supporting a small electrical
load (
 10%), the UPS shuts down the load. After three minutes in Sleep mode, the UPS
initiates a shutdown warning (two beeps every two seconds). This feature conserves
battery power. To enable this feature, contact your service representative.
UPS Configuration
Your PW5125 UPS can be configured by using a configuration software that can be find
on web (www.emea.powerware.com/product/PW5125.htm). This software is a DOS
based program that can be executed from either a DOS box, from a Windows shortcut,
or from the Windows Start, Run dialog box.
UPS setting that can be changed are as follow:
1.
Voltage setting 220/230/240 V (230 V is factory default)
2.
Enable/disable sleep mode (disable as factory default)
3.
Enable/disable audible alarm, so that when disable no audible alarms will be given
(Enable as factory default)
4.
Enable/disable site wiring detection (not supported on European model)
Turning the UPS On
After the UPS is connected to a power outlet, it conducts a self–test and enters Standby
mode. To turn on the UPS, press and hold the On  button until you hear the UPS beep
(approximately one second). The 
 indicator stops flashing and the bar graph
indicators display the percentage of load being applied to the UPS.
Starting the UPS on Battery
NOTE  Before using this feature, the UPS must have been powered by utility power at
least once.
To turn on the UPS without using utility power, press and hold the On button for at least
four seconds. The UPS supplies power to your equipment and goes into Battery mode.