UPS SYSTEM INSTALLATION
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
4−6
Left Top Panel
Wireway Panel
Left Middle Panel
Corner Channel
UPM Section
Interior Left
Side Panel
Figure 4-5. Section Joining
5.
Remove the screws securing the left top panel and remove the panel (see
Figure 4-5). Retain the hardware for later use.
6.
Remove the screws securing the left middle panel and remove the panel (see
Figure 4-5). Retain the hardware for later use.
C
 
A
 
U
 
T
 
I
 
O
 
N
Use care during installation to protect components mounted on the right side of the ISBM section and the
intercabinet wiring harnesses attached to the left side UPM section from damage.
NOTE  Clearance between the ISBM and the UPM sections must be less than 1/2" so that joining brackets
can be installed.
7.
Using a forklift with the forks in the front forklift slots, position the ISBM section
adjacent to the left side of the previously installed UPM section. Verify that the
ISBM section right side is against the UPM section left side and the front of the
cabinet bases are flush with each other (see Figure 4-6).
8.