Powerware 400/230V User Manual

Page of 72
OPERATION
EATON Powerware
®
 Energy Management System (EMS) Upgrade Kit User’s Guide  
S
  164201724 Rev 1
 www.powerware.com
43
Control Panel Configuration
NOTE  Use this section only if the optional display is installed.
To set up branch circuit monitoring on your product, configure the panels
and branch circuit breakers. Configuration requires System Setup
Level 1 password access.
Accessing Configuration
To access the configuration options at System Setup Level 1:
1.
In the Setup menu, select ENTER PASSWORD.
2.
Use the arrow keys to enter the password (default password is L1
for Level 1).
3.
Select DONE. The screen displays the setup options.
To change the default password while logged into System Setup Level 1
access:
1.
In the Setup menu, select CHANGE ACCESS LEVEL PASSWORD.
2.
Use the arrow keys to enter the new password (A–Z, 0–9, –, blank).
3.
Select DONE.
Configuring Panels Containing Branch Circuit Breakers
To configure panels containing branch circuit breakers:
1.
If not already obtained, access the System Setup Level 1 password
level. See the previous section, Accessing Configuration."
2.
From the main menu, select METER then PANEL.
3.
On the PANEL screen, select the panel number (PNL) to configure,
and then select CONFIG.