Connecting Equipment to a Serial Port
You can connect a wide variety of terminals, printers, and computers to each port,
and configure the UPS as the Data Communication Equipment (DCE). Set up the
remote equipment using the appropriate parameters for the mode you select. The
following section provides more information about configuration.
The cables you use for connection depend on the equipment you are connecting
to the UPS. Cables should be no longer than 16m (50 ft). The connectors for
Port 1 and Port 2 on the Communications Panel in the UPS are female, so the
cables should be male. Figure 41 shows the pin assignments for Port 1, and
Table 2 describes them. Figure 42 shows the pin assignments for Port 2, and
Table 3 describes them.
3
2
1
5
4
7
6
9
8
+24V
RS232 TXD
RS232 RXD
NOT USED
RETURN
NOT USED
485 +
485 --
RETURN
PORT 1 (DB--9)
Figure 41. Port 1 Pin Assignments
Table 2. Pin Assignments for Port 1 (DB---9)
Pin # Symbol
Description
Comments
1
+24V
+ 24 volts DC
2
TXD
Transmit Data
Input to UPS
3
RXD
Receive Data
Output from UPS
5
RTN
Return
7
485+
RS485 + Data
8
485---
RS485 --- Data
9
RTN
Return