Powerware 5075 kVA User Manual

Page of 162
89
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio
n
164201261 Rev. F 111503
Configuring the Serial Ports
You must configure the port for communications using the LCD screen and
pushbuttons on the UPS Monitor Panel.
Select
Port 1 or Port 2 (optional) from the Setup menu to display one of the Setup
Port screens. The screens for Port 1 and Port 2 are identical, and allow you to
specify settings for the two serial communication ports. Figure 43 shows the Setup
Serial Port 1 screen.
Statistics Graphics
Setup
Setup
Port 1
Uninterruptible Power System
UPS System Normal
Alarm:
None
Notice: None
03 JAN 1994 14:23:45
Events
Meters
Setup Serial Port 1
Rate
9600
Data/Stop
8
1
Handshaking
XON / XOFF
Save
NO
Time
Mode
TERMINAL
Port 2
Battery
100%
Percent
Figure 43. Setup Serial Port 1 Screen
A small return arrow ( ) appears in the upper right corner of the Setup Port screen.
This arrow is a reminder that you can press the
pushbutton on the Monitor
Panel to toggle the pushbuttons between the menu box and the information area.
If the scroll bar is in the menu box, press the
pushbutton to toggle to the
information area. The first setting (Mode) is highlighted. Press the
or
pushbutton to move the highlight to the setting you want to change. To scroll
through the available options for that setting, press the
or
pushbutton.
To save the settings upon exit from this screen, be sure the Save field is set to YES.