Powerware 650825 kVA User Manual

Page of 192
EATON Powerware
®
 9395 UPS (650–825 kVA) Installation and Operation Manual  
S
  164201725 Rev 2 www.powerware.com
10−1
Chapter 10
Product Specifications
10.1
Model Numbers
The UPS is housed in a free-standing cabinet, divided into two sections with safety
shields behind the door and front panels. The UPS is available in 50 or 60 Hz with
various output power ratings.
Models
Power Rating
Frequency
Powerware 9395−825/650
650 kVA
50/60 Hz
Powerware 9395−825/750
750 kVA
50/60 Hz
Powerware 9395−825/825
825 kVA
50/60 Hz
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
10.2
Specifications
10.2.1
UPS Input
Operating Input Voltage
400 Vac
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc
Figure 10Table 10