PRODUCT SPECIFICATIONS
EATON Powerware
®
9395 UPS (650–825 kVA) Installation and Operation Manual
S
164201725 Rev 2 www.powerware.com
10−2
10.2.2
UPS Output
UPS Output Capacity
100% rated current
Output Voltage Regulation
"1% (10% to 100% load)
Output Voltage Adjustment
(Nominal +/–3%)
(Nominal +/–3%)
400 Vac nominal, adjustable from 388 Vac to 412 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
5% maximum THD (nonlinear load)
Output Current
Output Voltage Balance
3% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
Displacement
3° for 100% maximum load imbalance (linear load)
Output Transients
"5% (10% to 100% load)
Frequency Regulation
"0.1 Hz free running
Synchronous to Bypass
+10% to −10%
"3%
Frequency Slew Rate
1 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.8 pF Lagging
0.8 pF Lagging
Overload Capability
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
125% for 30 seconds
150% for 10 seconds
10.2.3
UPS Environmental
Operating Temperature
0 to 40°C (32 to 104°F) without derating. The recommended
operating temperature is 25°C (77°F).
operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self-discharge)
causes rapid battery self-discharge)
Relative Humidity (operating and
storage)
storage)
5% to 95% maximum noncondensing
Acoustical Noise
76 dB at a 1m distance, A weighted
EMI Suppression
Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD)
Immunity
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse
without damage and with no disturbance or adverse effect to the
critical load.
without damage and with no disturbance or adverse effect to the
critical load.