Powerware 9315 UPS User Manual

Page of 84
Communication
7−11
EATON Powerware
®
 9315 UPS (200–300 kVA) Operation Manual  
S  164201036 Rev G  www.powerware.com
7.6.3
Meters Printout – [Ctrl]+[M]
This key sequence prints the current readings of the UPS system meters. The input area
shows the phase-to-phase voltage, frequency, and phase current of the incoming utility,
followed by the kVA, kW, and power factor measurements. The output area shows the
same information for the power being output by the UPS. The Bypass area shows the
phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V)
and the DC current (I). Figure 7-7 shows a sample Meters printout.
Input
Output
Bypass
Battery
VAB
480
VBC VCA
KW
379
KVA
399
IA
IB
IC
FREQ
60.0
PF
0.95
V
540
I
0
480
480 480
480
480
VAB
480
VBC
VCA
480
480
IA
IB
IC
361
361
361
IN
0
VAB
480
VBC
VCA
480
480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Uninterruptible Power System
UPS System Normal
Alarm:  None
Notice:  None
03 JAN 1997  14:22:49
+
Figure 7-7. System Meters