Powerware 9315 UPS User Manual

Page of 84
Communication
7−12
EATON Powerware
®
 9315 UPS (200–300 kVA) Operation Manual  
S  164201036 Rev G  www.powerware.com
7.6.4
System Information Printout – [Ctrl]+[A]
This key sequence prints a listing of all available serial data. This printout contains the
information shown on the Event History Log and System Meters screens of the UPS (both
Figure 7-6 and Figure 7-7).
7.6.5
Battery Test Printout – [Ctrl]+[B]
This key sequence prints the Battery Test Log. The log consists of a history of the last
30 battery tests that were run and the results of those tests. The most recent test appears
at the bottom of the log. Figure 7-8 shows a sample of the Battery Test Log.
Uninterruptible Power System
UPS System Normal
Alarm:  None
Notice:  None
12 NOV 1997  15:39:31
UPS # 1
AUG 14 23:45
498.0
1.00 0000
SEP 11 23:45
498.0
1.00 0000
OCT  9 23:45
498.0
1.00
0000
NOV 13 23:45
498.0
0.99
0000
DEC 11 23:45
498.0
0.99
0000
JAN  8 23:45
498.0
0.98
0000
FEB 12 23:45
498.0
0.98
0000
MAR 12 23:41
000.0
0.00
0003
APR  9 23:45
496.2
0.98
0000
Battery Test Log
Date/Time
Volts
Health
Data
Figure 7-8. Battery Test Log
The Date/Time field is the date and time of the battery test.
The Volts field is a measured value of the battery voltage during the test. This field
displays 000.0 if the test did not run to completion.
The Health field is a relative measurement of the battery condition. This number can be
used to chart the condition of the batteries. If a sudden change of this number occurs
relative to the previous test results, it is an indication that the batteries may need
attention. This display is 0.00 if the test does not run to completion.
The Data field is a value to be used by your field service engineer to gain more information
about the battery tests.
If the battery test does not complete, the Volts and Health field reads zero and the UPS
Event History Log reports either Battery Test Failed, Battery Test Aborted (Load), or Battery
Test Aborted (Utility). If the test ran to completion, Battery Passed Test appears in the UPS
Event History Log.