Powerware 9315 UPS User Manual

Page of 84
Communication
7−15
EATON Powerware
®
 9315 UPS (200–300 kVA) Operation Manual  
S  164201036 Rev G  www.powerware.com
7.7.4
Customize Alarm Messages
If Customize Alarm Messages is selected from the Program Building Alarm menu, you can
select a custom message for a building alarm or disable a previously enabled building
alarm custom message. When this entry is selected, the following menu is displayed:
Customize Alarm Messages
Enabled on Building Alarm Number(s)
2 3
Enter Building Alarm Number:
This example indicates that there are custom messages enabled for Building Alarms 2
and 3. When a building alarm number is entered, the message being used by the software
is displayed (either a custom message or the default message indicated by the list of
enabled custom messages). If 1 was entered at the prompt, the following text appears:
Building Alarm Active Message: Building Alarm 1 (default
message)
Enter New Message or <CR> for No Change:
At this level you can enter a custom message, 30 characters maximum, to display when
Building Alarm 1 is activated. If a custom message is entered to activate the building alarm,
a custom message should also be entered to deactivate. After the message or a carriage
return is entered, the following is displayed:
Building Alarm Clear Message:  Clear Building Alarm 1
(default message)
Enter New Message or <CR> for No Change:
At this prompt, the user should enter the custom message for the building alarm
deactivation state. When a message or a carriage return is entered, the following text
appears:
Enter E to Enable Custom Message
Enter D to Disable Custom Message
Enter <CR> for No Change
Enter Selection:
If an E is entered at the prompt, the custom messages are used for the building alarm. If a
D is entered, the default messages are used for the building alarm.