Powerware 9315 UPS User Manual

Page of 84
Communication
7−16
EATON Powerware
®
 9315 UPS (200–300 kVA) Operation Manual  
S  164201036 Rev G  www.powerware.com
7.7.5
Program Unit Name
If Program Unit Name is selected from the main menu, the following is displayed:
Program Unit Name
Unit Name:
Enter New Name or <CR> No Change:
NOTE  Unit Name is 45 characters maximum.
The current unit name is displayed on the second line of the display and in the headers of
prints from Terminal mode. If a change is desired, the new unit name should be entered at
the prompt. The unit name is 45 characters maximum and includes spaces and any
punctuation. If the user wants to center the text portion of the name, the appropriate
number of leading spaces should be included when entered.
7.7.6
Adjust Output Voltage
If Adjust Output Voltage is selected from the main menu, the following menu is
displayed:
Adjust Output Voltage
Output Voltage Setup:  480
Output Voltage Range:  456 − 504
Enter Desired Output Voltage Setup:
The output voltage desired can then be entered or a carriage return for no change. Only
values within the range are accepted.
7.7.7
Change Password
If Change Password is selected from the main menu, the following menu is displayed:
Change Password
Enter New Password:
Verify New Password:
NOTE  Password must be six characters in length.
<CR> to return with no change.
The password changes if the user enters and verifies the password. The entry must be six
characters.