9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
Chapter 6
Installing Options and Accessories
6.1 Installing a Hot Sync Computer Area Network Bridge Card
As an option, a Hot Sync CAN Bridge Card, as shown in Figure 6-1, can be installed to
provide connectivity for operational mode control and metering of a parallel system at any
UPM in the system. In addition, this card can be used to connect an optional system
monitoring device, such as a Remote Monitor Panel, a Relay Interface Module, or
Supervisory Contact Module to the UPS.
Plug-In Terminal
Block J3
Figure 6-1. Hot Sync CAN Bridge Card
1. Verify the UPS system is turned off and all power sources are removed. See
Chapter 10, “UPS Operating Instructions,” for shutdown instructions.
2. If not already open, unfasten the front door latch and swing the door open.
3. Install the Hot Sync CAN Bridge Card into an open X-Slot on the front of the UPS.
Remove the X-Slot cover panel to gain access to the X-Slot. See Drawing
164201535-8 starting on page A-33 for location of the X-Slot communication bay.
4. Proceed to paragraph 6.2.