E6581343  ③ 
- 18 - 
3.6.1.3.  Example 3. Reading the status monitor parameter (fe02 (The operation frequency)) 
 
AK = 6 (Request parameter value (array)) 
SPM = 0 
PNU = 1 
IND = 0xFE02(fe02 communication number) 
 
PKE 
0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 
6 0 0 1 
 
Requirement 
PKW PZD 
PKE IND  PWE 
60 01 FE 02 00 00 00 00 ・・・ 
・・・
 
 
Response (Value: 0x03E8 (= 1000 -> 10.00Hz)) 
40 01 FE 02 00 00 03 E8 ・・・ 
・・・
 
 
* The status monitor parameter can not be changed. 
 
 
3.6.1.4.  Example 4. Changing the basic parameter (acc (acceleration time)) 
 
AK = 7 (Change parameter value (array word)) 
SPM = 0 
PNU = 1 
IND = 0x0009 (acc communication number) 
 
PKE 
0 1 1 1 0 0 0 0 0 0 0 0 0 0 0 1 
7 0 0 1 
 
Requirement (acc = 7.0 sec. -> 70 (= 0x0046)
*
PKW PZD 
PKE IND  PWE 
70 01 00 09 00 00 00 46 ・・・ 
・・・
 
 
Response 
40 01 00 09 00 00 00 46 ・・・ 
・・・
 
 
* When the “Acceleration time” is set to 7.0 sec., set the following value. 
(The unit of the “Acceleration time” is 0.1s.) 
7.0/0.1 = 70 = 0x0046 (hexadecimal number)