Toshiba PDP002Z User Manual

Page of 28
E6581343  ③ 
- 19 - 
4. ”USER DEFIND” Profile 
Cyclic command transmission (the value of the parameter f831 - f836) and 
monitoring (the value of the parameter f841 - f846) are possible for PDP002Z 
by the original profile 
 
Select the ”USER DEFIND” as the profile on the configuration.   
Refer to the PLC configurator documents.
 
 
 
f831
 - f836 setup value 
f841
 - f846 setup value 
0: No action 
1: FA06 (ALCAN2 command 1) 
2: FA23 (ALCAN2 command 2) 
3: FA07 (ALCAN2 frequency command, 0.01Hz) 
4: FA33 (Torque command, 0.01%) 
5: FA50 (Terminal output) 
6: FA51 (Analog output (FM) data from comm.) 
7: FA52 (Analog output (AM) data from comm.) 
8: F601 (Stall prevention level, %) 
9: F441 (Power running torque limit 1 level, 0.01%) 
10: F443 (Regenerative braking torque limit 1 level, 0.01%)
11: F460 (Speed loop proportional gain) 
12: F461 (Speed loop stabilization coefficient) 
0: No action 
1: FD01 (Inverter status 1) 
2: FD00 (Output frequency, 0.01Hz) 
3: FD03 (Output current, 0.01%) 
4: FD05 (Output voltage, 0.01%) 
5: FC91 (Inverter alarm) 
6: FD22 (PID feedback value, 0.01Hz) 
7: FD06 (Input terminal status) 
8: FD07 (Output terminal status) 
9: FE36 (VI/II input) 
10: FE35 (RR/S4 input) 
11: FE37 (RX input) 
12: FD04 (Input voltage (DC detection), 0.01%) 
13: FD16 (Speed feedback (real-time value) 
14: FD18 (Torque, 0.01%) 
15: FE60 (My monitor) 
16: FE61 (My monitor) 
17: FE62 (My monitor) 
18: FE63 (My monitor) 
19: F880 (Free notes) 
20: FD29 (Input power, 0.01kW) 
21: FD30 (Output power, 0.01kW) 
22: FE14 (Cumulative operation time, 1 hour) 
23: FE40 (FM terminal output monitor) 
24: FE41 (AM terminal output monitor)