13)  Additional warnings and notifications shall be posted at the equipment installation location as 
deemed required by Qualified Personnel
 
CAUTION 
When the UPS is in the Inverter mode, turning the breaker to the OFF 
position will cause the unit to go into the battery backup mode. The 
 
UPS will continue to provide power to the load. The unit must be in Bypass mode and then 
the breaker turned to the OFF position for the UPS to shut down power to the load. 
CAUTION 
Do not EPO (Emergency Power OFF) the UPS and then reset the 
breaker until the UPS has been fully discharged. The UPS could be 
damaged if the unit is not fully powered down before the breaker is 
reset.
 
4.0 UPS Connections 
4.1  
Power Connections  
 
4.1.1 
Power Connections 15/25/30 kVA with Internal Batteries 
  The following illustrates the wiring connections from the power distribution panel (not part 
  of the UPS) to the terminal block of the 15/25/30 kVA UPS Models 
 
 
CUSTOMER-PROVIDED AC DISTRIBUTION PANEL 
INPUT GROUND RESISTANCE 
LESS THAN 10 OHMS 
TB1 
TB4 
Optional Bypass Input: 
3-phase, 3-Wire 
*208 V requires 3-phase, 
4-Wire Wye 
4200FA CT/XT User’s Manual 
 
 
20