4.1.3 
Recommended Wire Size and Torque Requirements 
 
 
UPS Input and Output Terminals 
 
Minimum Wire Size and Torque Requirements 
 UPS Input and Output Terminals 15/25/30 kVA 
(USE MINIMUM 75 °C INSULATED COPPER WIRING) 
15 kVA 
25 kVA 
30 kVA 
 Phase:  (A)   (B)   (C) 
Input: (H1) (H2) (H3) 
AWG Torque AWG
 
Torque AWG
 
Torque 
208 V 
51 in-lbs. 
51 in-lbs. 
87 in-lbs. 
220 V 
51 in-lbs. 
51 in-lbs. 
87 in-lbs. 
240 V 
51 in-lbs. 
51 in-lbs. 
87 in-lbs. 
380 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
400 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
415 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
480 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
600 V 
10 
35 in-lbs. 
10 
35 in-lbs. 
10 
35 in-lbs. 
All wire sizes are per the NEC.  Maximum Wire Size is 2 AWG. 
15 kVA 
25 kVA 
30 kVA 
Output:  
(L1) (L2) (L3) (N) 
AWG 
(L1)-
(L3) 
AWG 
(N) 
Torque 
(inch-lbs.) 
(L1)-(L3)     (N)  
AWG
(L1)-
(L3)
 
AWG
(N) 
Torque 
(inch-lbs.) 
(L1)-(L3)  (N)  
AWG 
(L1)-
(L3)
 
AWG
(N) 
Torque 
(inch-lbs.) 
(L1)-(L3)  (N) 
120/208 
V  8 4  51  51 4 2 51 87 2  2 87 87 
127/220 
V  8 4  51  51 4 2 51 87 2  2 87 87 
240 
8 N/A  51  N/A 4 N/A 51 N/A  2  N/A 87 N/A 
220/380 
V  10 8  35 
 51 8 4 51 51 6  2 51 87 
230/400 
V  10 8  35 
 51 8 4 51 51 6  2 51 87 
240/415 
V  10 8  35 
 51 8 4 51 51 6  2 51 87 
277/480 
V  10 8  35 
 51 8 6 51 51 6  2 51 87 
600 
10 N/A  35 
  N/A 10 N/A  35  N/A  10  N/A  35 N/A 
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC.  Maximum Wire Size is 2 
AWG. 
15 kVA 
25 kVA 
30 kVA 
 
Input/ Output (GND) 
AWG 
Torque 
AWG
Torque 
AWG 
Torque 
(G) 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
Maximum Wire Size is 2 AWG. 
 
Minimum Wire Size and Torque Requirements 
UPS Optional Separate Bypass Input “TB4” 15 / 25kVA 
(USE MINIMUM 75 °C INSULATED COPPER WIRING) 
15 kVA 
25 kVA 
30 kVA 
Phase:  (A)   (B)   (C) 
Input: (H1) (H2) (H3) 
AWG Torque AWG
Torque AWG
 
Torque 
208 V 
51 in-lbs. 
51 in-lbs. 
87 in-lbs. 
220 V 
51 in-lbs. 
51 in-lbs. 
87 in-lbs. 
240 V 
51 in-lbs. 
51 in-lbs. 
87 in-lbs. 
380 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
400 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
415 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
480 V 
10 
35 in-lbs. 
51 in-lbs. 
51 in-lbs. 
600 V 
10 
35 in-lbs. 
10 
35 in-lbs. 
10 
35 in-lbs. 
Maximum Wire Size is 2 AWG. 
 
 
 
4200FA CT/XT User’s Manual 
 
 