DISPLAY DURATION SET 
<3 MIN>            30 MIN 
>
Δ/∇: CHANGE DATA 
>ENTER:ACCEPT  CHANGE
 
 
Press the 'up' or 'down' arrow key to move the marker between the two available idle mode 
 
times. Press the ENTER key to save the change or press the MENU key to exit to the main 
 
menu and discard the change. 
 
 
Note:
  If any of the following conditions occur, the LCD-Idle Mode will be inhibited and the
 
LCD will remain on continuously: 
1)  The UPS has received an EPO command. 
2)  The UPS is in Battery-Discharge Mode. 
3)  A fault has been detected in the main unit. 
4)  The UPS is in an overload condition. 
 
 
6.19.4  Run Switch Select 
 
Press the MENU key to access the menu data screens and press the 'down' arrow key to 
 
scroll to the “Run Switch Select” setting screen display: 
 
 RUN  SWITCH  SELECT 
   <LOCAL>      REMOTE 
>*F1: DATA  SET  MODE 
>
Δ/∇: PRV/NEXT SCREEN 
  
 
Press the F1 key to display the following active adjustment screen: 
 
  RUN  SWITCH  SELECT 
    <LOCAL>      REMOTE 
>
Δ/∇: CHANGE  DATA 
>ENTER:ACCEPT  CHANGE 
 
 
Press the 'up' or 'down' arrow key to move the marker between the two "RUN SWITCH" 
 
selections Press the ENTER key to save the change or press the MENU key to exit to the 
 
main menu and discard the change. (Must have Remote Control option.) 
 
6.19.5  Serial Com Station Address 
 
Press the MENU key to access the menu data screens and press the 'down' arrow key to 
 
scroll to the “Serial Comm Station Address” setting screen display: 
 
SER  COM  STATION  ADDR 
STATION  ADDRESS:     31H 
>*F1: DATA SET MODE 
Δ/∇: PRV/NEXT SCREEN 
  
 
Press the F1 key to display the following active adjustment screen: 
 
SER  COM  STATION  ADDR 
STATION  ADDRESS:     31H 
>Δ/∇: CHANGE DATA 
>ENTER: ACCEPT  CHANGE 
 
4200FA CT/XT User’s Manual 
 
 
55