APC SMX3000RMLV2UNC User Manual

Page of 20
Smart-UPS X 2000/2200/3000 VA  
10
Audible Alarm On
On/Off
The UPS will never beep if all audible 
alarms are set to Off or when the display 
buttons are pressed.
Auto Self-Test 
Interval Setting
On start-up and every 14 
days since the last test
• Last test + 14 days
• Last test + 7 days
• Turn on + 14 days
• Turn on + 7 days
• On startup only
• Never
The interval at which the UPS will execute a 
self-test. The batteries much be charged to at 
least 70% capacity to perform the test.
Reset to Factory 
Default
No
Yes/No
Restore the UPS factory default settings.
Function
Factory Default
Options
Description