Siemens DataNET Hub (DNH) User Manual

Page of 97
 
2000585-001 
Installation 
••••  21 
Site Wiring Requirements, 
Continued 
 
The following information pertains when using copper wire 
See Page 23, CE Installations 
Use approved Conduit wiring method. Conduit may contain multiple ca-
bles. Adhere to all Federal and local electrical code requirements.  
Cable Type: Refer to Table 2-1. 
Use Cable Gland wiring method. Each cable gland allows entry of one 
cable. 
Cable Type: Recommend Belden 9182 or armored Belden 9182 or 
equivalent. The proper cable gland must be used to connect the armor or 
shield to the HUB enclosure. Other cables with individually shielded pairs 
can be used, but decreased distance is allowed (typically ~800-1000 feet 
for typical instrumentation cable). 
Use approved flexible non-metallic conduit wiring method. Conduit may 
contain multiple cables. For CE installations use only cable gland wiring 
method. 
Cable Type: Recommend Belden 9182 or equivalent. Other cables with 
individually shielded pairs can be used, but decreased distance is al-
lowed (typically ~800-1000 feet for typical instrumentation cable). 
 
The DataNET channel connections can be either copper wire or fiber 
optic cable. The wiring method and cable type for DataNET is dependent 
upon the site requirements. The following pertains when using copper 
wire. 
See Page 23,CE Installations 
Use approved Conduit wiring method. Conduit may contain multiple ca-
bles. Adhere to all Federal and local electrical code requirements.  
Cable Type: Duplex fiber, 62.5/125 micron; see Table 2-1. 
Connection: Type ST fiber connectors. Connect these to the appropriate 
transmitter and receiver ports for the respective channel.  
Copper Wire Site 
Requirements 
CE Installations 
NEC Div 2 or Non-
Hazardous Rated Areas  
Cenelec Zone 1 or Zone 2 
Rated Areas 
Non-Hazardous Areas or 
Rack Mounting 
DataNET Fiber Optic 
Cable Connections 
CE Installations 
NEC Div 2 or Non-
Hazardous Areas