APC 990 User Manual

Page of 32
Operation: Operation Procedures
10
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001
Press the Startup button. Press inside the password 
field and type in the user password using the 
keyboard on the screen. Complete with Enter.
The UPS Startup screen appears with the Charge DC 
Capacitors step highlighted. Follow the procedure 
on the screen which is specific to your system.
Verify that the status in the upper right corner has 
changed to Normal.
How to shut down the system from normal to manual bypass operation
Note: The UPS Shutdown screen on this page shows an example of a generic shutdown 
sequence. Follow and complete the shutdown sequence as shown on your UPS Shutdown 
screen.
Press the Operation button on the UPS Summary 
screen.