Press Initiate Transfer.
Verify that the status in the upper right corner of the 
screen has changed to Static bypass.
How to transfer from static bypass to normal operation
Press the Operation button on the UPS Summary 
screen.
Press the Static Bypass -> Online button. Press 
inside the password field and type in the user 
password using the keyboard on the screen. 
Complete with Enter.
Press Initiate Transfer.
Verify that the status in the upper right corner of the 
screen has changed to Normal.