Fujitsu C122-E119EN User Manual

Page of 109
TABLE A.2 Recommended racks for mounting
Fujitsu 19-inch rack
Depth (mm)
Open area ratio
Model 2742
1050
80%
Model 2737
1050
80%
Model 2724
1050
80%
Model 2642
1050
80%
Model 2624
1050
80%
Model 2616
1050
75%
Model 1740
1050
80%
Model 1640
1050
80%
Model 1624
1050
80%
 
TABLE A.3 PRIMEQUEST 1000 series external dimensions*
Model
Height
Width
Depth
PRIMEQUEST 1800E2/1800E
530 mm
(12U)
440 mm
(Panel included:
482 mm)
800 mm
* The external dimensions do not include protrusions.
 
Note
The Fujitsu 19-inch rack comes with a blank panel covering the front of each empty space that has no mounted
device.
If warm exhaust air from the device circulates to the front of the rack and reenters the device, it may cause a
temperature alarm and lead to a device failure.
Be sure to use the blank panel to cover the front of an empty space that has no mounted device.
 
Rack mounting requirements
The following table lists the requirements for mounting in one rack.
 
TABLE A.4 Rack mounting requirements
Model
Number of
mountable units
Mounting area
PRIMEQUEST 1800E2/1800E
Up to 2 units
The bottom of the mounted device
must not be below 1U.
The top of the mounted device must
not be above the upper limit (26U).
(*)
PCI_Box
No mounting requirements (*)
PRIMEQUEST 1000 Series Hardware Installation Manual
APPENDIX A Racks
52
C122-H004-07EN