SECTION 4 ADJUSTMENTS
4--1
Time Delay Adjustment
Standard time delays are set to customer specifications
(if none specified, standard factory settings are used).
To change a setting, follow procedure on page 4-2. Use
Table 4-1 as a guide to time delay values and their corre-
sponding adjustment DIP switch or potentiometer.
Table 4-1. Time Delay Settings
DESCRIPTION
LABELS
FACTORY
SETTING
ADJUSTMENT
RANGE
S3 DIP
SWITCH
ADJUSTMENT
POTENTIOMETER
Override Momentary
TD ES
3 seconds
1 second
Actuator 1 on
1
Override Momentary
Normal Source Outages
TD ES
3 seconds
3 seconds
Actuator 1 off
1
Transfer to Emergency
TIMER
0 minutes
0 to 5
P2
Transfer to Emergency
TIMER
N/E
0 minutes
(full ccw)
0 to 5
minutes
P2
Override Momentary
Emergency S. Outages
4 seconds
non-adjustable
Retransfer to Normal
TIMER
30 minutes
1 second to
P1
Retransfer to Normal
TIMER
E/N
30 minutes
(full cw)
1 second to
30 minutes
P1
Unloaded Running
(Engine Cooldown)
5 minutes
non-adjustable
Sensor Adjustments
Voltage and frequency sensor pickup and dropout
points are set to customer specifications (if none
specified, standard factory settings are used). To change
a setting, follow procedure on page 4–2. Use Tables 4-2
and 4–3 for settings and corresponding DIP switch
actuators.
NOTICE
Any change in these settings may affect the
normal operation of the automatic transfer
switching equipment. This change could allow
the load circuits to remain connected to a low
voltage source.
Table 4-2. Voltage and Frequency Settings. (
Shaded DIP switches are standard factory settings).
DESCRIPTION
LABELS
SETTING
% of nominal
S1 DIP
DESCRIPTION
LABELS
SETTING
FACT. SET
ADJ RANGE
S1 DIP
SWITCH
PU / N
Pickup
90 %
95 % *
Actuator 3 off
3
PU / N
Pickup
90 %
90 %
Actuator 3 on
3
90 % *
Actuator 1 off
Actuator 2 off
2
1
Normal Source Voltage
DO / N
Dropout
85 %
85 %
Actuator 1 on
Actuator 2 off
2
1
DO / N
Dropout
85 %
80 %
Actuator 1 off
Actuator 2 on
2
1
70 %
Actuator 1 on
Actuator 2 on
2
1
Emergency Source Volt-
– –
Pickup
90 %
non-adjustable
Emergency Source Volt
age
– –
Dropout
75 %
non-adjustable
– –
– –
Pickup
95 %
non-adjustable
Emergency Source
– –
Dropout
85 %
non-adjustable
– –
Emergency Source
Frequency
60 / 50
60 / 50 Hz
60 Hz
60 Hz
Actuator 4 off
4
eque cy
60 / 50
Hz
60 / 50 Hz
60 Hz
50 Hz
Actuator 4 on
4
Voltage Phases
3 4 1 4
3 4 / 1 4
3 4
3 phase
Actuator 6 off
6
Voltage Phases
3 4 , 1 4
3 4 / 1 4
3 4
1 phase
Actuator 6 on
6
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTION
LABELS
FACTORY SETTING
ADJUSTMENT
S3 DIP SWITCH
Voltage Adjust (4 2%)
LOW /
HI
LOW
Actuator 2 off
2
Voltage Adjust (4.2%)
LOW /
HI
HI
HI
Actuator 2 on
2