Schneider Electric Class 615 User Manual

Page of 76
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
 
Section 9—Accessories
© 1995–2003 Schneider Electric All Rights Reserved
28
AUXILIARY AND ALARM SWITCHES
Changeover 
Switches
Auxiliary switches provide remote information of the circuit breaker status and can thus be used for 
indications, electrical locking, relays, etc.
Functions
OF (open/closed): auxiliary switch—indicates position of the circuit breaker contacts
SD (trip indication): bell alarm—indicates that the circuit breaker has tripped due to
— Overload
— Short circuit
— Ground fault
— The operation of a shunt trip or undervoltage trip or the "push-to-trip" button which resets when 
the circuit breaker is reset
Operation of a plug-in base or chassis when attempting to withdraw the circuit breaker in ON 
position; SDE (fault indication): indicates the circuit breaker has tripped due to an overload, short 
circuit or ground fault; resets when circuit breaker is reset
CAM (early-make or early-break function): indicates the position of the rotary handle; used in 
particular for advanced-opening safety trip devices
Connected/disconnected: indicates the position of a drawout circuit breaker
Switching of very low loads: all above auxiliary switches are also available in low-level versions 
capable of switching very low loads (e.g., for controlling PLCs or electronic circuits)
Standards
Auxiliary switches comply with UL 489, CSA C22.2 No. 5.1 and IEC 947-5 Standards. “Low-level" 
switches are not UL Listed.
Installation
Functions OF, SD and SDE:
— Switches snap into cavities under front accessory cover of the circuit breaker
— For Compact
®
 NSF150–NSJ600 circuit breakers, one model serves for all indication functions 
depending on where it is fitted in the circuit breaker
SDE function of a circuit breaker equipped with a thermal-magnetic trip unit requires the SDE 
actuator
CAM: to be fitted in the rotary handle module; depending on how it is installed, it ensures either the 
CAO (early-break) or the CAF (early-make) function "Connected/disconnected" function; two parts 
to be fitted on the chassis and the drawout circuit breaker
0
6153
101