Schneider Electric Class 615 User Manual

Page of 76
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 9—Accessories
© 1995–2003 Schneider Electric All Rights Reserved
29
Electrical Ratings
UL 489 and CSA C22.2 No. 5.1 Ratings
Low-level Switches
Regular Switches
Minimum Rating
1 mA–4 V
10 mA–24 V
Maximum Current and Voltage
100 mA–10 V
6 A–480 V
If the maximum voltage and 
current are exceeded, the low-
level characteristics of the switch 
will be compromised. However, 
the switch will still function as a 
standard switch to the following 
specifications:
Maximum Rating
50/60 Hz
240 V
5
6
480 V
5
6
600 V
3
DC
48 V
2.5
2.5
125 V
0.8
0.8
250 V
0.3
0.3
IEC 947 Ratings
Low-level Switches
Regular Switches
Rated Thermal Current (A)
5
6
Minimum Rating
1 mA–4 V
10 mA–24 V 
Maximum Current and Voltage
100 mA–10 V
6 A–480 V
If the maximum voltage and current are 
exceeded, the low-level characteristics of 
the switch will be compromised. 
However, the switch will still function as a 
standard switch to the following 
specifications:
ac
dc
ac
dc
Utilization Category
(IEC 947-4)
AC12
AC15
DC12
DC14
AC12
AC15
DC12
 DC14
Operational Current (A)
24  V
5
3
5
1
6
6
2.5
1
48 V
5
3
2.5
0.2
6
6
2.5
0.2
110 V
5
2.5
0.8
0.05
6
5
0.8
0.05
220/240 V
5
2
6
4
250 V
0.3
0.03
0.3
0.03
380/415 V
5
1.5
6
3
440 V
5
1.5
6
3
660/690 V
6
0.1