2. Water-Cooled Condenser
a) Connection to an Open Drain System
• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" nominal 
copper water tubing is recommended for the condenser water supply line.
• A condenser water supply line shut-off valve and drain valve should be installed.
• Condenser drain outlet is 3/8" FPT. A minimum of 3/8" nominal hard pipe is recommended 
for the condenser drain line.
• In some areas, a back flow preventer may be required in the cooling water circuit.
• In order to maintain the proper high side pressure, the condenser water supply inlet 
temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature 
must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation 
is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze 
cycle starts. If the condenser drain outlet temperature is not in the proper range, use a 
flat blade screwdriver to rotate the adjustment screw on the water-regulating valve until 
the temperature is in the proper range (rotate counterclockwise to raise temperature or 
clockwise to lower temperature).
Fig. 9
KM-1400SWH/3-M 
Connection to an Open Drain System
Separate piping to approved drain. 
Leave a 2-inch (5-cm) vertical air 
gap between the end of each pipe 
and the drain.
Icemaker Water Supply Line 
Shut-Off Valve
Icemaker Water Supply Line 
Drain Valve
Icemaker
Icemaker 
Water Supply 
Inlet
1/2" FPT
2-inch (5-cm) air gap
Floor Drain
Icemaker
Drain Outlet 
3/4" FPT
Bin
Condenser Water Supply Line 
Shut-Off Valve
Condenser Water Supply Line 
Drain Valve
Condenser Water 
Supply Inlet
1/2" FPT
Condenser 
Drain Outlet 
3/8" FPT
Condensation 
Drain Outlet
3/8" OD Hard Tube
Minimum 1/2" Nominal Copper Water Tubing
Vent Tube
Vent Tube
Minimum 
3/4" Nominal 
Hard Pipe
Minimum 3/8" Nominal 
Hard Pipe
Minimum 3/8" Nominal Copper Water Tubing
Bin Drain Outlet
See Manufacturer's Instructions