Using a Line Contactor or an Output Contactor
When controlling the power with a line isolation contactor, avoid frequently 
opening and closing the line contactor as this could cause premature failure 
of the drive controller. Use inputs LI1 to LI4 to start and stop the drive 
controller. Limit operations of the line contactor to less than once per minute.
To use an output contactor, use the wiring diagram to the left for guidance 
and set relay R2 to the Output Contactor Command function. In the wiring 
diagram at left, the shaded portion is to be added to the output of either the 
single-phase wiring diagram or the three-phase wiring diagram on page 108.
The recommended output contactors are shown in the table below.
KM2
KM2
ATV58H•••••
LC1-
ATV58H•••••
LC1-
U09M2
D25
U18N4
D25
U18M2
D25
U29N4
D25
U29M2
D25
U41N4
D25
U41M2
D25
U72N4
D25
U72M2
D25
U90N4
D25
U90M2
D25
D12N4
D25
D12M2
D32
D16N4
D25
D23N4
D4011
D16M2
D40
D28N4
D40
D23M2
D80
D33N4
D50
D28M2
D80
D46N4
D80
D33M2
D80
D54N4
D8010
D46M2
F115
D64N4
F115
D79N4
F115
Refer to the Digest for control voltage information.
U
V
W
U1
W1
V1
M
 3 Phase
R2A
KM2
R2C
KM2
TS
120 VAC
TS = Transient suppressor
LineCont.eps
Wiring Diagram for Output Contactor
See Specifications section for 
contactor ratings.