External RFI Input Filters
NOTE: Line reactors and filters are intended for separate mounting and wiring by the user. Ratings are 
based on NEC (NFPA 70) 430-150 current ratings. If the drive has a higher FLA rating, use the “A” rating 
to select the appropriate filter.
Supply Voltage
ATV58 Models
Maximum Length of
Shielded Cable
[1]
Nominal 
Current (In) 
of the Filter 
Weight
Catalog 
Number
EN 55011 
Class A
EN 55022 
Class B
Single-Phase
200 to 240 Vac
50/60 Hz
ATV58•U09M2, ATV58•U18M2
50 m/164 ft
20 m/65 ft
10 A
1.7 kg/3.7 lb
VW3A58401
ATV58•U29M2, ATV58•U41M2
50 m/164 ft
20 m/65 ft
25 A
3.6 kg/7.9 lb
VW3A58402
ATV58•U72M2
50 m/164 ft
20 m/65 ft
25 A
5.0 kg/11.0 lb
VW3A58403
ATV58•U90M2, ATV58•D12M2
50 m/164 ft
20 m/65 ft
40 A
10.0 kg/22.0 lb
VW3A58404
3-Phase
200 to 240 Vac
50/60 Hz
ATV58•U29M2, ATV58•U41M2
50 m/164 ft
20 m/65 ft
25 A
3.6 kg/7.9 lb
VW3A58402
ATV58•U54M2, ATV58•U72M2
50 m/164 ft
20 m/65 ft
25 A
5.0 kg/11.0 lb
VW3A58403
ATV58•U90M2, ATV58•D12M2
50 m/164 ft
20 m/65 ft
45 A
10.0 kg/22.0 lb
VW3A58404
3-Phase
208 to 240 Vac
50/60 Hz
ATV58HD16M2X, ATV58HD23M2X
n/a
n/a
80 A
13.0 kg/28.6 lb
VW3A58407
ATV58HD28M2X, ATV58HD33M2X,
ATV58HD46M2X
n/a
n/a
160 A
20.0 kg/44.0 lb
VW3A58408
3-Phase
400 to 460 Vac
50/60 Hz
ATV58•U18N4, ATV58•U29N4, 
ATV58•U41N4
50 m/164 ft
20 m/65 ft
25 A
3.6 kg/7.9 lb
VW3A58402
ATV58•U54N4, ATV58•U72N4, 
ATV58•U90N4
50 m/164 ft
20 m/65 ft
25 A
5.0 kg/11.0 lb
VW3A58403
ATV58•D12N4, ATV58•D16N4
50 m/164 ft
20 m/65 ft
45 A
10.0 kg/22.0 lb
VW3A58404
ATV58•D23N4
50 m/164 ft
20 m/65 ft
45 A
13.0 kg/28.6 lb
VW3A58405
ATV58HD28N4
200 m/656 ft
100 m/328 ft
50 A
13.0 kg/28.6 lb
VW3A58406
ATV58HD33N4, ATV58HD46N4
200 m/656 ft
100 m/328 ft
80 A
13.0 kg/28.6 lb
VW3A58407
ATV58HD54N4, ATV58HD64N4, 
ATV58HD79N4
200 m/656 ft
100 m/328 ft
160 A
20.0 kg/44.0 lb
VW3A58408
[1] The filter selection tables give the maximum length for the shielded cables which connect the motors to the drive controllers for a switching frequency 
of 0.5 to 12 kHz. These limits are given for information only as they depend on the interference capacity of the motors and the cables used. For motors 
connected in parallel, the total of the lengths must be taken into account.
Line Reactors—480 V Rated Three Phase
460 V Drive Rating
Open Style 
Part Number
Enclosed 
Part Number
Approx. 
Wt. 
(lbs.)
Enclosure 
Dimensions 
HxWxD 
(in.)
HP
kW
1
. . .
RL00202
RL00212
11
8x8x6
2–3
. . .
RL00403
RL00413
12
8x8x6
5
. . .
RL00803
RL00813
18
15x13x13
7.5
. . .
RL01203
RL01213
25
15x13x13
10
. . .
RL01803
RL01813
49
15x13x13
15
. . .
RL02503
RL02513
49
15x13x13
20–25
. . .
RL03503
RL03513
61
15x13x13
30
. . .
RL04503
RL04513
70
15x13x13
40
. . .
RL05503
RL05513
72
15x13x13
50–60
. . .
RL08003
RL08013
86
15x13x13
75
. . .
RL10003
RL10013
105
15x13x13
100
. . .
RL13003
RL13013
105
15x13x13
125
. . .
RL16003
RL16013
105
15x13x13
150
. . .
RL20003
RL20013
131
15x13x13
200
. . .
RL25003
RL25013
185
24x17x17
250
. . .
RL32003
RL32013
235
24x17x17
300
. . .
RL40003
RL40013
245
24x17x17
350–400
. . .
RL50003
RL50013
335
24x17x17
450–500
. . .
RL60003
RL60013
335
24x17x17
Line Reactors