ATV58 TRX TYPE N DRIVE CONTROLLERS
The ATV58 TRX family of adjustable-frequency AC drive controllers is used 
to control three-phase asynchronous motors.The ATV58 TRX Type N models 
contain an ATV58 TRX Type H drive controller packaged in a Type 4/4x 
stainless steel enclosure. They are for use in food and beverage wash-down 
applications. The Type N drive controller was tested for corrosion resistance 
per UL-50 and exceeds this standard. The UL-50 corrosion test was 
conducted using ASTM B117-1985.
The following models are available:
• 1 to 10 hp (0.75 to 7.5 kW), 400/460 Vac, 3-phase input.
• ½ to 3 hp (0.37 to 2.2 kW), 208/230 Vac, single-phase input.
• ½ to 5 hp (0.37 to 4.0 kW), 208/230 Vac, 3-phase input.
Each Type N drive controller is furnished with four conduit openings that are 
closed with Type 4/4x plugs. The drive is available with a keypad mounted 
behind a transparent boot to allow viewing and operation of the keypad while 
maintaining the Type 4/4x rating. If a keypad is not required, a closing plate 
can be installed to maintain the Type 4/4x rating. All ATV58 TRX 
communication and I/O options can be used in the Type N controllers. The 
Type N drive controllers can be used on constant or variable torque 
applications. The ratings are shown in the tables below.
208 to 230 Vac, Single-Phase Input with 3-Phase Output
Frame 
Size
 
Drive Controller 
Catalog Number
Motor Power
Rated Output 
Current
Transient Output 
Current
kW
HP
A
A
1
ATV58NU09M2•
0.37
0.5
2.3
3.1
1
ATV58NU18M2•
0.75
1
4.1
5.6
2
ATV58NU29M2•
1.5
2
7.8
10.6
2
ATV58NU41M2•
2.2
3
11
15
208 to 230 Vac, 3-Phase Input with 3-Phase Output
Frame 
Size
Drive Controller 
Catalog Number
Motor Power
Rated Output 
Current
Transient Output 
Current
kW
HP
A
A
2
ATV58NU29M2•
1.5
2
7.8
10.6
2
ATV58NU41M2•
2.2
3
11
15
3
ATV58NU54M2•
3
13.7
18.6
3
ATV58NU72M2•
4
5
18.2
24.7
400 to 460 Vac, 3-Phase Input with 3-Phase Output
Frame 
Size
Drive Controller 
Catalog Number
Motor Power
Rated
Output Current
Transient Output 
Current
kW
HP
A
A
2
ATV58NU18N4•
0.75
1
2.3
3.1
2
ATV58NU29N4•
1.5
2
4.1
5.6
2
ATV58NU41N4•
2.2
3
5.8
7.9
3
ATV58NU54N4•
3
7.8
10.6
3
ATV58NU72N4•
4
5
10.5
14.3
3
ATV58NU90N4•
5.5
7.5
13
17.7
4
ATV58ND12N4•
7.5
10
17.6
24
Complete the catalog number by entering KU for ATV58 Type N drive controllers with factory-installed keypad, 
or ZU for controllers without a factory-installed keypad. For dimensions, see page 122; for wiring diagrams, see 
page 108.
Power indicated is for a switching frequency between 0.5 and 4 kHz, and at steady state. For switching 
frequency between 8 and 16 kHz, derate the drive controller by one horsepower size (for example, for ½ hp, 
order drive controller ATV58NU18M2). If the duty cycle (i.e., drive controller run time) does not exceed 60% 
(36 second maximum for a 60 second cycle), derating is not required for operation above 8 kHz.
For 60 seconds.
When these drive controllers are used with a single-phase input, a line reactor (3% minimum) must be used.
ATV58 TRX Type N Product Family
A
T
V
5
8N
E
M
A
4
X
b
_w
 n
o
 ba
c
k
.t
if