Schneider Electric 58 TRX User Manual

Page of 232
Class 8839 58M Enclosed AC Drives
Specifications
175
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
ENCLOSED ADJUSTABLE FREQUENCY 
DRIVES (1 TO 500 HP)
Note to Specifier: These specifications apply to 
Enclosed Adjustable Frequency Drive Controllers, 
herein referred to as AC Drives. The power 
converter is a component of the AC Drive. To 
ensure project compatibility, these specifications 
follow the Construction Specifications Institute 
(CSI) format. Copies of this specification are 
available from the Square D
®
 website, 
www.squared.com. Application information 
directly affects the type and rating of AC Drive that 
will be quoted. [Brackets] are provided where 
such data and options should be included or 
considered depending on application 
requirements. Please contact your local Square D 
distributor or sales representative for specification 
assistance regarding a particular application. The 
AC Drive specification should be included in 
Division 16 (Electrical) for proper coordination 
with the electrical distribution sy
stem.
PART 1 GENERAL
1.01 SCOPE OF WORK
a. This section provides specification 
requirements for adjustable frequency drives, 
variable speed drives or herein identified as 
AC Drives for use with NEMA
®
 B design AC 
motors.
b. The AC Drive manufacturer shall furnish, field 
test, adjust and certify all installed AC Drives 
for satisfactory operation.
c. Any exceptions/deviations to this specification 
shall be indicated in writing to the specifying 
engineer and submitted with the quotation.
1.02 REFERENCES
a. NFPA-70 (2002) “National Electric Code 
(NEC
®
)”
b. ANSI C84.1 (R2002) “Electric Power Systems 
and Equipment - Voltage Ratings (60Hz)”
c. CSA
®
 C22.2 No.14-95 (R2001) “Industrial 
Control Equipment”
d. UL508A (2003) “Standard for Safety for 
Industrial Control Panels”
e. UL508C (2002) “Standard for Safety for Power 
Conversion Equipment”
f.
NFPA 79 (2002) “Electrical Equipment of 
Industrial Machines/Industrial Machinery
g. NEMA ICS7 (2000) “Industrial Control and 
Systems: Adjustable Speed Drives
h. NEMA ICS7.1 (2000) “Safety Standards for 
Construction and Guide for Selection, 
Installation, and Operation of Adjustable 
Speed Drive Systems
i.
NEMA 250 (1997) “Enclosures for Electrical 
Equipment (1000V maximum
j.
IEC 61800-2 (1998-03) “Adjustable speed 
electrical power drive systems - Part 2: 
General requirements - rating specifications 
for low voltage adjustable frequency AC power 
drive systems” 
k. IEC 61800-3 (1998-06) “Adjustable speed 
electrical power drive systems - Part 3: EMC 
product standard including specific test 
methods” 
l.
IEC 61800-5-1 (2003-02) “Adjustable speed 
electrical power drive systems - Part 5-1: 
Safety requirements - Electrical, thermal and 
energy
m. IEC 61800-6 (2003-03) “Adjustable speed 
electrical power drive systems - Part 6: Guide 
for determination of types of load duty and 
corresponding current ratings.” 
n. EGSA 101P (1995a) “Engine Driven 
Generator Sets - Performance Standard”
o. IEEE 519 (1992) “Recommended Practices 
and Requirements for Harmonic Control in 
Electrical Power Systems”
1.03 SUBMITTALS
a. [6] copies of approval drawings shall be 
furnished for Engineer’s approval prior to 
factory assembly of the AC Drives. These 
drawings shall consist of elementary power 
and control wiring diagrams and enclosure 
outline drawings. The enclosure drawings 
shall include front and side views of the 
enclosures with overall dimensions and 
weights shown, conduit entrance locations 
and nameplate legend details.
b. Standard catalog sheets showing voltage, 
horsepower, maximum current ratings and 
recommended replacement parts with part 
numbers shall be furnished for each different 
horsepower rated AC Drive provided.