DESCRIPTION OF CONTROL TERMINALS
All ATV58 TRX Type E, Type F, Type H, and Type N models have the same 
control terminals, shown in the figure to the left. The locations of the control 
terminals varies from model to model as shown on pages 18 and 19.
The control terminal strip contains two pull-apart terminal blocks, one for the 
relay outputs and one for the low-level inputs and outputs. The S terminal is 
used for the shield connection. Maximum wire size for all control terminals is 
14 AWG (1.5 mm
2
). Tightening torque is 3.5 lb-in (0.4 N•m). The 
characteristics of the control terminals are shown in the table below.
Terminal Function
Characteristics
R1A
R1B
R1C
R1A to R1C is a N.O. contact. When the 
drive controller is powered with no fault, 
the contact is closed.
R1B to R1C is a N.C. contact. When the 
drive controller is powered with no fault, 
the contact is open.
Min.: 10 mA, 24 Vdc
Max. inductive load: 1.5 A for 250 Vac and 30 Vdc
Max. resistive load: 5 A for 250 Vac or 30 Vdc
R2A
R2C
N.O. programmable relay R2
S
Shield connection
COM
Common for logic and analog inputs
AO1
Analog current output
X–Y mA analog output, with X and Y 
programmable from 0–20 mA.
Factory setting: 0–20 mA.
Maximum load impedance = 500 
Ω
Resolution: 0.04 mA (9 bits)
Linearity: +/- 0.1 mA
Accuracy: +/- 0.2 mA
The analog output is updated every 2 mS, maximum.
AI1
Analog input 1 (voltage)
Used for speed reference input
0 to 10 Vdc, Impedance = 30 k
Ω
Frequency resolution analog reference: 
(high speed/1024) Hz (10 bit)
Accuracy ±1%, linearity ±0.5% of the maximum output 
frequency
Sampling time: 5 ms
Optically isolated
+10
Supply for reference potentiometer 
(1 to 10 k
Ω
)
10 V ± 1%, protected against short circuits and overloads
10 mA maximum
AI2
Programmable analog input
Used for speed reference input or 
feedback, depending on configuration.
X to Y mA, with X and Y being programmable from 
0 to 20 mA (factory setting: 0 to 20 mA)
Impedance = 100 
Ω
Frequency resolution analog reference: 
(high speed/1024) Hz (10 bit)
Accuracy ±1%, linearity ±0.5% of the maximum output 
frequency
Sampling time: 5 ms
Optically isolated
LI1
LI2
LI3
LI4
Programmable logic inputs
Function depends on configuration.
Supplied by +24 Vdc
State 0 if < 5 V, state 1 if > 11 V
Vmax = 30 V
Impedance = 3.5 k
Ω
Sampling time: 5 ms
Optically isolated
+24
Power supply for logic inputs
+24 V protected against short circuits and overloads
Minimum 20 V, maximum 30 V
200 mA maximum
ATV58 TRX Control Terminals
R1A
R1B
R1C
R2A
R2C
AO
1
COM
AI1
+10
AI2
LI1
LI2
LI3
LI4
+24
S
T
e