Schneider Electric 58 TRX User Manual

Page of 232
Altivar
®
 
58 TRX AC Drives
I/O Extension Cards
31
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
AO
1
COM
AI1
+10V
AI2
LI1
LI2
LI3
LI4
+24V
SW1
SW2
SW3
SW4
AO1 COM AI1 +10V
AI2
ACI1 ACI2 ACI3 ACI4 ACCOM
115 V
~
Top of the logic 
input module
Control terminal strip 
Module 
terminal block
NOTE: 115 Vac is 
present at these five 
terminals.
DC control wiring 
AC control wiring 
in
p
u
t w
ir
in
g
.e
p
s
115 Vac Logic Input Module Typical Wiring
115 VAC Logic Input Module (VW3A58275U)
The 115 Vac logic input module, catalog number VW3A58275U, makes it 
possible to use ATV58 TRX control terminal points LI1, LI2, LI3, and LI4 with 
control circuits that require 115 Vac control. The module insolates the 
115 Vac signals from the 24 Vdc input signals of the drive controller terminal 
strip, without modifying the other signals.
The 115 Vac logic input module is designed for use only on the Type H and 
Type N families of ATV58 TRX drive controllers. It requires no special 
programming.
Drive controller logic inputs LI1, LI2, LI3, and LI4 retain their functionality 
when using this module. These inputs correspond to the module inputs 
labeled ACI1, ACI2, ACI3, and ACI4 respectively.
The figure at the left shows typical wiring using four switches, operating on 
115 Vac, as inputs to the drive controller. Power is derived from a 115 Vac 
power source wired to the switches, then to inputs ACI1–ACI4. The 115 Vac 
common must be connected to the ACCOM terminal on the module.
See the table below for electrical specifications. The module accepts 
26–16 AWG (0.14–1.3 mm
2
) wire.
ACI1 
ACI2 
ACI3 
ACI4
Frequency
47 to 63 Hz
Input Impedance
28 k
Ω ±
10% @ 25 °C (77 °F)
Maximum Allowable 
Voltage Range
0–132 Vrms
Input to Guarantee On 
State
90 to 132 Vrms
Input to Guarantee Off 
State 
a
a. Coupling can cause voltages higher than 50 Vrms, which can turn the 
input on or prevent it from turning off. 
0 to 50 Vrms
Storage Temperature